PFS Apollo air make-up unit installed on a rooftop

Air Make-Up Units

PFS air make-up units supply tempered, filtered replacement air to spray booths and finishing rooms — maintaining proper airflow balance and code compliance.
Air Make-Up Units

Choose Your Configuration

Proper air replacement is required by OSHA and NFPA 33 for any spray booth. PFS manufactures heated and non-heated AMUs for every climate and application.
air-makeup-unit
Gas-fired or electric heated AMUs for cold climates and temperature-sensitive coatings. Available with natural gas, propane, or electric heat sources. Required for booths operating in sub-freezing environments.
PFS Apollo non-heated air make-up unit

Designed to bring fresh outside air into the paint booth. Non-tempered. Heated options available upon request.

HEAT SOURCE OPTIONS

Heated AMU Heat Sources Compared

Every PFS heated AMU is sized for your booth airflow and climate. Here is how the heat sources compare.
Heat sourceBest forNotes
Natural gasProduction shops with gas serviceThe most common choice. Direct-fired or indirect-fired burners, high heat output and low operating cost.
PropaneRemote sites, outdoor booths, no natural gasSame performance as natural gas, configured for a propane supply.
ElectricSites without gas, clean rooms, sensitive facilitiesNo combustion and precise digital temperature control; lower heat output ceiling than gas.
Non-heatedMild climates and processes that do not need tempered airSupplies fresh, filtered outside air. Heat can be added on request.
AIR MAKE-UP GUIDE

How to Choose an Air Make-Up Unit

Use these notes to narrow down the right unit, then let our team confirm the CFM and heat load at no charge.

A spray booth exhausts a large volume of air to carry overspray and solvent vapor outside. The air make-up unit (AMU) brings the same volume of fresh, filtered air back in. Without it the building goes negative: doors are hard to open, dust and dirt are pulled in through every gap, the booth starves for air and the finish suffers.

The AMU is sized to the booth exhaust in cubic feet per minute (CFM). Booth CFM comes from the booth airflow area and the design air velocity, so a larger booth or a downdraft booth with a full ceiling plenum needs more air. Most booths are balanced slightly positive so clean supply air, not shop air, fills the booth. See our air make-up unit guide for the details.

If the booth runs in cold weather, or the coating needs a stable temperature to flow out and flash, choose heated AMUs. Heating capacity is set by airflow and temperature rise: BTU/h is about 1.08 × CFM × the rise from the coldest outdoor temperature to your setpoint. In mild climates, non-heated AMUs supply fresh outside air at ambient temperature.

Direct-fired gas units put the burner in the airstream, so nearly all the heat goes into the supply air. Indirect-fired units heat the air through a heat exchanger, so combustion products never enter the booth. The choice depends on the application, local code and the fuel available.

Paired with the booth control panel, a heated AMU can run separate spray, flash and cure temperatures. That is how heated paint booths shorten cure cycles and keep production moving through the winter.

OSHA and NFPA 33 require replacement air for spray booths, and the AMU is interlocked with the booth exhaust so spraying cannot start without ventilation. Gas-fired units also need the gas train, flame safeguard and permits your jurisdiction requires. See our NFPA 33 guide.

FREQUENTLY ASKED QUESTIONS

Air Make-Up Units: Common Questions

In most cases, yes. A booth exhausts thousands of cubic feet of air every minute, and OSHA and NFPA 33 require that air to be replaced. An AMU does that with filtered air, keeps the building from going negative and keeps the booth airflow steady.

By the booth exhaust CFM, and for heated units by the temperature rise from your coldest outdoor design temperature to the booth setpoint. Send us the booth size and type and your location and we will size it.

Heated if the booth runs in cold weather or the coating needs a controlled temperature. Non-heated where the climate is mild and tempered air is not needed. A non-heated unit can be ordered with heat added.

Natural gas, propane and electric. Gas units are available as direct-fired or indirect-fired.

Usually. We check the booth exhaust CFM, the duct path and the controls, then size the AMU and interlock it with the existing exhaust fan.

Not Sure Which AMU You Need?

Our team will size the right unit for your booth CFM, climate, and heat source — at no charge.